What are the overload ratings of the WC1?
The overload ratings for the WC1 are 110% for 60 seconds in Normal Duty (ND) operation and 150% for 60 seconds in Heavy Duty (HD) operation.
The overload ratings for the WC1 are 110% for 60 seconds in Normal Duty (ND) operation and 150% for 60 seconds in Heavy Duty (HD) operation.
The enclosure rating for the WC1 is UL Type 1, which is suitable for wall-mounted or panel-mounted installations.
A conduit adapter is not required for UL Type 1, as it is included with the unit.
The ambient temperature rating for the WC1 is -15°C to 50°C without derating. Operation up to 60°C is permitted with reduced output current.
The altitude rating for the WC1 is up to 2000 m (6600 ft) without derating.
The humidity rating for the WC1 is up to 95%, non-condensing.
The WC1 is UL and cUL listed. CE and CSA certifications are not currently available.
The WC1 does not support single-phase input and is designed for three-phase operation only.
The WC1 supports Modbus TCP and BACnet IP as standard communication protocols. Ethernet/IP will be available in a future software release.
A separate remote keypad is not required, as the standard keypad is detachable and can be remotely mounted.